DWDM over CWDM: 42 x 10G on one fiber pair
Overview
Fiber is often the most limited resource in metro, enterprise and data center interconnect networks, and a CWDM link that has used up its 18 channels usually means new fiber or a full DWDM rebuild. This solution avoids both. It keeps the CWDM MUX/DEMUX in place and turns two of its channels, 1531 nm and 1551 nm, into windows that each carry a full group of DWDM channels. EDGE supplies the complete passive path: the DCMD-18 CWDM MUX/DEMUX, the DDMD-11-5161 with 11 DWDM channels (C51 to C61) on the 1531 nm port, and the DDMD-15-2640 with 15 DWDM channels (C26 to C40) on the 1551 nm port. Together they give 16 CWDM and 26 DWDM channels, 42 x 10G on one fiber pair. Capacity grows with a transceiver order, not a construction project. EDGE Optical Solutions | Solutions page | SOL-06 draft v08, 2026-10-26 2 The DWDM units connect to the DCMD-18 1531 nm and 1551 nm ports with A-to-B duplex patch cords.
Optical budget
The DWDM channels set the reach, because each one passes through two filters at every site. The calculation assumes a fiber loss of 0.25 dB/km in the C-band and at 1471 nm to 1611 nm, 0.35 dB/km at 1271 nm to 1451 nm (G.652.D fiber, splices included), and 1.0 dB for connectors and patch cords along the path. The DWDM-10G-SFP-100 transceivers have a 26 dB optical budget. In the 1531 nm window, the two DCMD-18 units (2.2 dB each) and the two DDMD-11-5161 units (4.0 dB each) account for 12.4 dB. A 40 km span adds 10.0 dB of fiber loss and the connectors 1.0 dB, for 23.4 dB in total and 2.6 dB of margin. The 1551 nm window has less loss: 4.4 dB for the DCMD-18 pair plus 7.0 dB for the two DDMD-15-2640 units (3.5 dB each), 22.4 dB in total at 40 km, leaving 3.6 dB of margin. On the CWDM side only the 4.4 dB of the DCMD-18 pair is in the path. At 40 km the 1271 nm to 1451 nm channels see 14.0 dB of fiber loss, 19.4 dB in total against the 26 dB budget of the CWDM-10G-SFP-100, a 6.6 dB margin. The rated reach of these optics, 40 km on the 1351 nm to 1451 nm channels, sets the 40 km limit for the whole system.
Alternatives and notes
If fewer CWDM services are enough, the DCMD-8-4761 (IL 1.5 dB) can replace the DCMD-18. It carries the same two DWDM units for 6 CWDM and 26 DWDM channels and reaches about 48 km. For a standard channel plan with more guard band, the DDMD-8-5360 and DDMD-8-2936 give 8 DWDM channels per window, 16 in total. The solution is passive only, with no amplifier or dispersion compensation anywhere in the path.
Bill of materials
Every product in the diagram above, with the quantity each one appears. Open a row for full specifications, pricing and ordering.
- 2xDCMD-1818-channel double-fiber passive CCWDM mux/demux, 19" 1U rack-mount housing, ITU-T G.694.2, monitor port, LC/UPC connectors.
- 2xDDMD-1111-channel double fiber 100GHz DWDM mux/demux for the ITU-T C-band, selectable channel band, optional 1310nm window port, LC/UPC connectors, EXP port, 19-inch 1U rack mount.
- 2xDDMD-1515-channel double fiber 100GHz DWDM mux/demux for the ITU-T C-band, selectable channel band, optional 1310nm window port, LC/UPC connectors, EXP port, 19-inch 1U rack mount.
- 8xCWDM-10G-SFP-100CWDM 10G SFP+ Module (Tx/Rx 1470-16101270-1610nm, 1.25-11.32 Gbps, Max. 100km over SMF, 26 dB, 2000 psnm, Temp. 0-70C, LC/UPC)
- 8xDWDM-10G-SFP-100DWDM 10G SFP+ Module (Tx/Rx 17-61, ITU Grid: C-Band 100 Ghz, 1.25-11.32 Gbps, Max. 100km over SMF, 26dB, Temp. 0-70C, LC/UPC)
- 1xLC/UPC-LC/UPC-OS2-DX-B-LSZH-XLC/UPC to LC/UPC, Type A to B, Duplex, OS2 9/125μm, LSZH Patch cable, Length 0.5-100 meter